GROUNDING TOOL LA-AT
The main objective of its installation is to protect the worker from accidental
energization or possible backfeed during repair work.
Composition of:
(2) SNAP-ON CLIPS DUCK-BILL TYPE for Grounding Aluminum body,
serrated jaws, bronze screw with eyelet, bronze terminal.
(1853 -Salisbury)
ELECTRICAL VALUES (60 Hz)
Continuous Current: 400 A
Fault current (60Hz): 15 Cycles - 43 kA // 30 Cycles - 30 kA
MECHANICAL VALUES
Recommended torque: 300 lbf in
Allowable Main Line Sizes – Max 1.625" (ACSR 1590 kcmil)
Allowable Main Line Sizes – Min 0.5"
Bridge Allowable Sizes – Max Ground Cable 4/0 with Threaded Lug
Bridge Allowable Sizes – Min Ground Cable #2 with Threaded Lug
Approx. weight: 0.8 Kg.
ASTM Designation Type I Class B Grade 5.
(1) COPPER GROUNDING CABLE
Copper cable with clear jacket Length 5.00
meters AWG 1/0 conductor count 1045 /
Diameter (Approx. in) 0.410 Exterior diameter
Approx. in 0.66 Weight Approx. 425 lb/1000 ft
(CA1/0-TR -Luztom)
(2) TERMINAL LUG 1/0 SCREWED
compliant to: IEC
61230:2008
ASTM F855
IEEE-1048-2016
*Integrated by PowerSafe