top of page

GROUNDING TOOL LA-AT

The main objective of its installation is to protect the worker from accidental

energization or possible backfeed during repair work.


Composition of:

(2) SNAP-ON CLIPS DUCK-BILL TYPE for Grounding Aluminum body,

serrated jaws, bronze screw with eyelet, bronze terminal.

(1853 -Salisbury)

ELECTRICAL VALUES (60 Hz)

Continuous Current: 400 A

Fault current (60Hz): 15 Cycles - 43 kA // 30 Cycles - 30 kA

MECHANICAL VALUES

Recommended torque: 300 lbf in

Allowable Main Line Sizes – Max 1.625" (ACSR 1590 kcmil)

Allowable Main Line Sizes – Min 0.5"

Bridge Allowable Sizes – Max Ground Cable 4/0 with Threaded Lug

Bridge Allowable Sizes – Min Ground Cable #2 with Threaded Lug

Approx. weight: 0.8 Kg.

ASTM Designation Type I Class B Grade 5.

(1) COPPER GROUNDING CABLE

Copper cable with clear jacket Length 5.00

meters AWG 1/0 conductor count 1045 /

Diameter (Approx. in) 0.410 Exterior diameter

Approx. in 0.66 Weight Approx. 425 lb/1000 ft

(CA1/0-TR -Luztom)

(2) TERMINAL LUG 1/0 SCREWED


compliant to: IEC

61230:2008

ASTM F855

IEEE-1048-2016


*Integrated by PowerSafe


    Other customers also looked at...

    Need more information?

    CONTACT US

    5 - CONTACTANOS - FLECHA.png

    POWERSAFE® All rights reserved

    Terms and Conditions